Borehole thermal energy storage systems represent a potential solution to increase the energy efficiency of renewable energy plants, but they generally have to comply with strict regulatory frameworks, mainly due to the deliberate modification of the subsoil's natural state. This paper presents the design, testing, and monitoring phases carried out to set up a borehole thermal energy storage (BTES) system able to exploit the excess solar heat from photovoltaic thermal (PVT) collectors. The case study is the refurbishment of a pig nursery barn, hosting up to 2500 weaners, in Northern Italy. This study aims to define a BTES suitable to develop a heating system based on renewable energy, ensuring environmental protection and long-term sustainability. The retrofitting intervention includes the installation of a dual-source heat pump (DSHP), in order to recover the solar heat stored in summer during winter. Specific constraints by the Environmental Authority were as follows: maximum storage temperature of 35 degrees C, authorization to intercept the shallowest aquifer at a maximum depth of 30 m, obligation of BHE grouting, and the definition of a strategy for continuous measuring and monitoring of the groundwater's thermophysical properties. The results were used as inputs to optimize the design and installation of the integrated system with PVT, BTES, and DSHP.

Development of a Pilot Borehole Storage System of Solar Thermal Energy: Modeling, Design, and Installation

Tinti F.
Primo
;
Rapti D.
Penultimo
;
2023

Abstract

Borehole thermal energy storage systems represent a potential solution to increase the energy efficiency of renewable energy plants, but they generally have to comply with strict regulatory frameworks, mainly due to the deliberate modification of the subsoil's natural state. This paper presents the design, testing, and monitoring phases carried out to set up a borehole thermal energy storage (BTES) system able to exploit the excess solar heat from photovoltaic thermal (PVT) collectors. The case study is the refurbishment of a pig nursery barn, hosting up to 2500 weaners, in Northern Italy. This study aims to define a BTES suitable to develop a heating system based on renewable energy, ensuring environmental protection and long-term sustainability. The retrofitting intervention includes the installation of a dual-source heat pump (DSHP), in order to recover the solar heat stored in summer during winter. Specific constraints by the Environmental Authority were as follows: maximum storage temperature of 35 degrees C, authorization to intercept the shallowest aquifer at a maximum depth of 30 m, obligation of BHE grouting, and the definition of a strategy for continuous measuring and monitoring of the groundwater's thermophysical properties. The results were used as inputs to optimize the design and installation of the integrated system with PVT, BTES, and DSHP.
2023
Tinti, F.; Tassinari, P.; Rapti, D.; Benni, S.
File in questo prodotto:
File Dimensione Formato  
2023_Tinti_et_alii_sustainability.pdf

accesso aperto

Descrizione: Full text editoriale
Tipologia: Full text (versione editoriale)
Licenza: Creative commons
Dimensione 7.88 MB
Formato Adobe PDF
7.88 MB Adobe PDF Visualizza/Apri

I documenti in SFERA sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/11392/2516890
Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 4
  • ???jsp.display-item.citation.isi??? 2