The results of an experimental campaign concerning full-scale tests on precast reinforced concrete column-to-column connections made with grouted sleeve splices are presented. The precast column units had a square cross-section with the side of 500 mm. Eight 20 mm-diameter bars protruding from one unit were grouted into corrugated steel sleeves encased in the other unit. The column-to-column connections were subjected to four monotonic tests (axial tension, bending with and without axial compression, and shear) and to one cyclic bending test. In the tension test failure took place far from the interface between the precast units and highlighted the effectiveness of the stress transfer along the splice region. In all other tests, damage developed at the interface between the two units. In the bending tests with and without axial compression significant over-strengths with respect to design resistances computed for equally-reinforced monolithic members were attained. Because of the reduced thickness of the interface between the precast units, the rotation that concentrated at the interface led to a moderate reduction of the global bending stiffness. In the shear test the pure shear capacity of the bars crossing the joint was achieved. The cyclic bending test showed a ductile and stable hysteretic behavior of the connection.

Grouted sleeve connections used in precast reinforced concrete construction - Experimental investigation of a column-to-column joint

TULLINI, Nerio
Primo
;
MINGHINI, Fabio
Ultimo
2016

Abstract

The results of an experimental campaign concerning full-scale tests on precast reinforced concrete column-to-column connections made with grouted sleeve splices are presented. The precast column units had a square cross-section with the side of 500 mm. Eight 20 mm-diameter bars protruding from one unit were grouted into corrugated steel sleeves encased in the other unit. The column-to-column connections were subjected to four monotonic tests (axial tension, bending with and without axial compression, and shear) and to one cyclic bending test. In the tension test failure took place far from the interface between the precast units and highlighted the effectiveness of the stress transfer along the splice region. In all other tests, damage developed at the interface between the two units. In the bending tests with and without axial compression significant over-strengths with respect to design resistances computed for equally-reinforced monolithic members were attained. Because of the reduced thickness of the interface between the precast units, the rotation that concentrated at the interface led to a moderate reduction of the global bending stiffness. In the shear test the pure shear capacity of the bars crossing the joint was achieved. The cyclic bending test showed a ductile and stable hysteretic behavior of the connection.
2016
Tullini, Nerio; Minghini, Fabio
File in questo prodotto:
File Dimensione Formato  
Grouted sleeve connections used in precast reinforced concrete construction – Experimental investigation of a column-to-column joint.pdf

solo gestori archivio

Descrizione: Full text editoriale
Tipologia: Full text (versione editoriale)
Licenza: NON PUBBLICO - Accesso privato/ristretto
Dimensione 4.98 MB
Formato Adobe PDF
4.98 MB Adobe PDF   Visualizza/Apri   Richiedi una copia
11392_2355786_POST_TulliniMinghini_2016.pdf

accesso aperto

Descrizione: Post print
Tipologia: Post-print
Licenza: PUBBLICO - Pubblico con Copyright
Dimensione 2.76 MB
Formato Adobe PDF
2.76 MB Adobe PDF Visualizza/Apri

I documenti in SFERA sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/11392/2355786
Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 146
  • ???jsp.display-item.citation.isi??? 123
social impact