This aim of the study was to identify effective levels of ClO2 for control of Legionella spp. contamination in the hot water (45-55 °C.) distribution system of a 579-bed hospital in Ravenna (Italy). Overall, 663 hot water samples were collected from the hospital's sinks and shower taps and were analyzed. Trend line analysis, which describes the trend in the number of positive samples collected according to disinfectant concentration, shows that the lowest number of positive samples was achieved with concentrations of ClO2 between 0.22 and 0, 32 mg /l.

[Evaluation of chlorine dioxide concentrations needed to effectively control contamination by Legionella spp in hospital hot water distribution systems]

RAVAIOLI, Cinzia;GABUTTI, Giovanni;STEFANATI, Armando
2016

Abstract

This aim of the study was to identify effective levels of ClO2 for control of Legionella spp. contamination in the hot water (45-55 °C.) distribution system of a 579-bed hospital in Ravenna (Italy). Overall, 663 hot water samples were collected from the hospital's sinks and shower taps and were analyzed. Trend line analysis, which describes the trend in the number of positive samples collected according to disinfectant concentration, shows that the lowest number of positive samples was achieved with concentrations of ClO2 between 0.22 and 0, 32 mg /l.
2016
Fusaroli, Paolo; Ravaioli, Cinzia; Gabutti, Giovanni; Caroli, Maria; Stefanati, Armando
File in questo prodotto:
Non ci sono file associati a questo prodotto.

I documenti in SFERA sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/11392/2350808
 Attenzione

Attenzione! I dati visualizzati non sono stati sottoposti a validazione da parte dell'ateneo

Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus ND
  • ???jsp.display-item.citation.isi??? ND
social impact